Parameters |
Values |
Power mains voltage supplied to input terminals, V |
~220±33 |
Frequency of power mains, Hz |
50±3 |
Voltage supplied to output terminals: direct or pulsating unipolar (amplitude value for a pulsating voltage), max, V |
100 |
Accepted current through built-up circuits of the input terminals, with peripheral devices (converters, rectifiers, cathodic protection stations, etc.), max, А |
32 |
Accepted current through built-up circuits of the output terminals, with peripheral devices (converters, rectifiers, cathodic protection stations, etc.), max, А |
100 |
Consumed current with nominal voltage of the power mains at the input terminals, max, mА |
0.1 |
Consumed current with nominal direct or pulsating unipolar voltage at the output terminals, max, mА |
30 |
Clamping voltage at varistors connected to the input terminals U and N, with ampere capacity of atmosphere (lightning) overvoltage with the duration of 8/20 mks and amplitude of 6000 А, V |
550...2000 |
Clamping voltage at varistors connected to the input terminal +А, with ampere capacity of atmosphere (lightning) overvoltage with the duration of 8/20 mks and amplitude of 6000 А, V |
550...1500 |
Clamping voltage at varistors connected to the input terminals +А and -Т, with ampere capacity of atmosphere (lightning) overvoltage with the duration of 8/20 mks and amplitude of 6000 А, V |
250...1000 |
Maximum cross section of two conductors mechanically connected to the unit with input terminals, mm2 |
10 |
Maximum cross section of two conductors mechanically connected to the unit with output terminals, mm2 |
35 |
Range of operating temperatures, °С |
from −45 to +45 |
Dimensions, mm |
394×344×100 |
Weight, max, kg |
7 |